Home
::
Accessories
::
Generator Remote Start / Stop Switch for petrol or diesel electric start generators
|
Generator Remote Start / Stop Switch for petrol or diesel electric start generators
DESCRIPTION
Start relay
0.5 second after the fuel relay is energized, the 3 attempt start will begin its start sequence: the start relay will energize, feeding battery +ve (on terminal 6) to terminal 7 and thence on to the starter circuit. The crank period is set for 12 seconds.If the engine has not fired by the end of 1st attempt, the starter is turned off for a 20 sec. period. The sequence will then repeat up to a maximum number of start attempts.
Following a successful start, sensed when AC alternator's voltage rises above 40% of nominal, the crank relay is de-energized and latched out to prevent reengagement of the starter with the engine running.
Should the engine still fail to start after the maximum number of attempts, FAIL TO START is displayed and the starter is latched out until reset via stop position of (rocker switch, selector switch, key switch where applicable).
Operation of the module is via (rocker switch, selector switch, key switch) mounted on the front panel with START and STOP positions or via remote start terminal 1.
Relay outputs are provided for:
The relays supply positive plant supply out.
Configurable inputs are available for:
Multiple alarm channels are provided to monitor the following:
These modules have been designed for front panel mounting.
The module is fitted into the cut-out with the fixing clips removed.
These are then fitted from the rear.
DC Supply: 8 to 33 V Continuous.
Max. Operating Current: 90 mA at 12 V. 87 mA at 24 V;
Max. Standby Current: 10 mA at 12 V. 10 mA at 24 V;
Alternator Input Range: 15 - 300 V ac RMS;
Low Frequency Limit:30 Hz;
High Frequency Limit: 57Hz;
Start Relay Output:
2 Amp DC at supply voltage.
Fuel Relay Output: 2 Amp DC at supply voltage.
Operating Temperature Range: -30 to +70°c